07/08/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
07/08/2024 Light Residential Building Review (OIP) REQUIRES RESUBMIT Show gas pipe sizes in compliance with connected demand, G2413.3 & Table G2413.4(1). Provide a gas line isometric or table for showing the BTU demand and length of line to each gas appliance. A gas range and dryer appliance is usually greater than 25,000 BTUs; verify the name plates. A 1000,000 BTU gas pack requires a 3/4" branch pipe size when the appliance developed length is greater than 20 feet. See the Gas Work templates at https://www.tucsonaz.gov/Departments/Planning-Development-Services/Permits/Residential-Permits