Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL SIMPLE REVIEW REVISION v.1
Permit Number - TC-RES-0724-03938
Review Name: RESIDENTIAL SIMPLE REVIEW REVISION v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/29/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 08/29/2024 | Light Residential Building Review (OIP) | REQUIRES RESUBMIT | Due to the new project scope, you will need to submit a new permit application for the additional gas line. Please include the following: 1.Provide a complete gas piping plan showing the connection and length from the meter to all attached appliances, G2401.1, R301.1: Include pipe size, type (Black Iron, Poly) and length. Connection must be shown to all appliances. Or show that the ¾” line to the range is a dedicated line from the meter. 2. Modifications or additions to the gas line may require that the existing system be enlarged to meet the total demand based on the new length, or a new dedicated line is required for the additional attached loads, G2412.3, G2412.4. 3. Note: The length is measured from the meter to the furthest attached appliance for all sizing, G2413.4.1. For questions: Building_Official@tucsonaz.gov |
||
| 08/29/2024 | PDSD Application Completeness Express | REVIEW COMPLETED |