Permit Number: TC-RES-0723-06934
Parcel: 121123540

Review Status: Requires Resubmit

Review Details: RESIDENTIAL NEW DWELLING v.1

Permit Number - TC-RES-0723-06934
Review Name: RESIDENTIAL NEW DWELLING v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/09/2023 Site Engineering NOT REQUIRED
08/15/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
08/14/2023 Residential Building REQUIRES RESUBMIT TC-RES-0723-06934
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. For facilitating a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. For facilitating a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

PROVIDE A COMPLETE PLAN SET showing all proposed alterations to the building with 2018 IRC code compliance with component sizes. The plans require sufficient detail for demonstrating an awareness of minimum building code compliance for passing all progress inspections.

SITE PLAN:

Provide a site plan showing dimensions of all buildings, R106.1.1. Show the location of all utility lines from property line to building(s) along with required alterations.

FLOOR PLAN:

Provide a floor plan showing each proposed room with labeled function and dimensions. Show door locations and window sizes with type identified as XO or SH. Include the identification of adjacent rooms with door or window openings in the proposed space. Bedroom windows must show code compliance for egress, R310.

STRUCTURAL PLANS:

1. Show one-hour fire-resistive framed construction separating dwellings in compliance with IBC Table 721.1(2).

PLUMBING PLANS:

1. Provide complete plumbing plans showing any changes with 2018 IRC compliance, R301.1.
2. Tucson Water Department limits flow rates for each water meter size in compliance with P2903.7. Show an appropriate yard pipe for supporting the existing and proposed dwelling units.
3. Show an individual accessible water supply shut off and water heater for the proposed dwelling building, P2903.9.1.

MECHANICAL PLANS:

1. Show heating facilities in all habitable rooms, R303.9.

ELECTRICAL PLANS:

1. Show two or more 2O AMP small appliance circuits at the kitchen countertop receptacle outlets; they may also serve the breakfast room and dining room, but not other locations, E3703.2 and E3901.3.

INTERNATIONAL ENERGY CONSERVATION CODE:

Provide insulation details minimum (R-13 walls and R-30 small additions or otherwise R-38 ceiling) showing code compliant placement of materials and ratings, N1101. Windows require a solar heat gain of 0.25 or better.

If you have any questions, please contact:
Ken Van Karsen
PDSD-Residential@tucsonaz.gov
City of Tucson Residential Plan Review

Submit a corrected plan set at https://www.tucsonaz.gov/Departments/Planning-Development-Services
08/15/2023 Site Zoning REQUIRES RESUBMIT PDSD TRANSMITTAL

FROM: Nathan Herrera
Planner

PROJECT: TC-RES-0723-06934
Address: 1654 N Rosemont Bl. Tucson, AZ. 85712
Parcel: 121-12-3540
Zoning: C-1
Existing Use: Residential Care Service
Project Description: Duplex

TRANSMITTAL DATE: 8/15/2023

This site is located in the C-1 zone (UDC 4.7.20). A single-family residence is a permitted use in this zone (Table 4.8-4).

1. COMMENT: Aerial imagery shows an existing wall on the south side of the property. Add the wall to the site plan and provide property line setback dimensions and wall height.

2. COMMENT: Aerial imagery shows a shed on the north side of the property. Add the shed to the site plan and provide property line setback dimensions and wall height.

3. COMMENT: Break out the lot coverage calculation per the Residential Plot Plan Requirements, found at https://www.tucsonaz.gov/files/sharedassets/public/pdsd/documents/permits/residential-permits/residential_plot_plan_requirements.pdf

4. COMMENT: Per UDC Section 7.4.4-1, the required amount of parking is 2 spaces per dwelling unit. Demonstrate on the site plan how the above requirement is being met.

Per UDC Section 7.4.6.B.3, tandem parking can be used to meet the requirement.

Per UDC Section 7.4.6.D, the minimum standard parking space size is 8.5 feet by 18 feet


RESUBMITTAL OF THE FOLLOWING IS REQUIRED: revised residential building permit along with a detailed response letter, which states how all Zoning Review Section comments were addressed. To resubmit visit Tucson Development Center at https://tdc-online.tucsonaz.gov/#/home. Instructions for resubmittal - https://www.tucsonaz.gov/files/sharedassets/public/pdsd/documents/tdc-faq/new-pdfs/revisions-and-resubmittals.pdf

If you have any questions about this transmittal, please contact Nathan Herrera at Nathan.Herrera@TucsonAZ.gov or 520-837-4894.
08/09/2023 PDSD Application Completeness Express REVIEW COMPLETED