Permit Number: TC-RES-0723-06912
Parcel: 140103280

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SOLAR v.1

Permit Number - TC-RES-0723-06912
Review Name: RESIDENTIAL SOLAR v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/03/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
08/03/2023 Light Residential Building Review (OIP) REQUIRES RESUBMIT Permit Review TC-RES-0723-06912 (2922 E ACACIA CLUB LN TUCSON, AZ 85706)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Residential Code (IRC).

1. Provide a clear and concise construction plan set. Many details are illegible and not all page numbers are consistent.
2. Provide a lag-bolt connection up-lift calculation demonstrating the wind load supporting capability, or provide an engineer’s calculation, and sealed design, R301.1, R324.4. An IRC PV roof uplift calculator (XLS) is available on Pima County’s website. https://www.pima.gov/1069/Solar-Wind-Systems
3. Equipment shall be positively attached to the roof structure with a minimum of one connection per 10 sf of equipment, R324.3, R324.4. Provide location of each mounting location and placement of the racking equipment.
4. 40A PV breaker must be at the opposite end of the bus bar from the main service breaker, 2017 NEC 705.12(B)(2)(3)(b).

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
08/01/2023 PDSD Application Completeness REVIEW COMPLETED