| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/24/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 07/24/2023 | Light Residential Building Review (OIP) | REQUIRES RESUBMIT | 1. Provide a site plan showing the overhead service conductor with appropriate clearance above accessory structures, E3604.2.1. 2. Provide a panelboard clear working space of 30” wide x 36” deep, E3405.2. 3. Panelboards shall not be in clothes closets, in bathrooms, E3405.5. Clarify the function of the wash room. |
||