Review Date Reviewer's Name Type of Review Description Status Comments
07/25/2023 Site Landscape NOT REQUIRED
08/03/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
08/03/2023 Residential Building REQUIRES RESUBMIT TC-RES-0723-06643
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. For facilitating a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. For facilitating a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

PROVIDE A COMPLETE PLAN SET showing all proposed alterations to the building with 2018 IRC code compliance with component sizes. The plans require sufficient detail for demonstrating an awareness of minimum building code compliance for passing all progress inspections.

Provide a clear and concise construction plan set. Sample plans are available at https://www.tucsonaz.gov/Departments/Planning-Development-Services/Permits/Residential-Permits

SITE PLAN:

Provide a site plan showing dimensions of all buildings and utilities, R106.1.1. Show the location of all utility lines from property line to building along with required alterations.

FLOOR PLAN:

Provide a floor plan showing each proposed room with labeled function and dimensions. Show door locations and window sizes with type identified as XO or SH. Include the identification of adjacent rooms with door or window openings in the proposed space. Bedroom windows must show code compliance for egress, R310.

STRUCTURAL PLANS:

1. Provide complete structural (roof framing) plans showing compliance with the IRC or provide an Arizona structural engineer plan set showing performance compliance, R301.1. Show all proposed repairs and alterations with 2018 IRC compliance, R301.1.

2. The proposed Patio Cover may be sited within the 3’ fire separation distance from a property line. Show compliance with R302.1 (City of Tucson Amended) by providing a wall with one-hour rated materials prescribed in IBC Table 721.1(2), Items 15-1.1 to 16-1.3, R106.1 or remove any structure closer than 3 feet to the property line.

SECTIONS - DETAILS:

1. Provide a structure section showing existing and proposed features including a foundation, anchoring, and dwelling connection, R106.1.

PLUMBING PLANS:

1. Provide complete plumbing plans showing any changes with 2018 IRC compliance including an accessible water supply shut off, P2903.9.1.

ELECTRICAL PLANS:

1. Provide a Riser Diagram showing a sub panel and feeder size extending from the service panel, NEC 225.30, E3403, Table E3704.2(1).

If you have any questions, please contact:
Ken Van Karsen
PDSD-Residential@tucsonaz.gov
City of Tucson Residential Plan Review

Submit a corrected plan set at https://www.tucsonaz.gov/Departments/Planning-Development-Services
07/25/2023 Site Zoning REQUIRES RESUBMIT ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
TC-RES-0723-06643 - CE-VIO0623-04155
7266 E. Paseo San Andres - R-1
Porch built w/o permit (1st Review)

TRANSMITTAL: July 25, 2023

Provided a detail comment response letter with your submittal that clearly shows how you have addressed all comments with your next submittal.

This site is located in the R-1 zone (UDC 4.7.8). A single-family residence is a permitted use in this zone (Table 4.8-2) subject to Use Specific Standards 4.9.7.B.5 – 9.

1. Provide a residential plot plan that meets the requirements found at: https://www.tucsonaz.gov/Departments/Planning-Development-Services/Building-Safety/Plan-Examples/Plot-Plan-Example.

2. Provide setback dimensions from the propose post supporting the porch to the property lines.

Additional comments maybe forth coming.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov