Permit Number: TC-RES-0723-06638
Parcel: 101235040

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SOLAR v.1

Permit Number - TC-RES-0723-06638
Review Name: RESIDENTIAL SOLAR v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/17/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
08/17/2023 Light Residential Building Review (OIP) REQUIRES RESUBMIT 1) Provide conductor sized according to E3705.5.3 Small conductors: Sheet PV-4, 4A, and 5 show a #10 AWG conductor for Raceways # 6, 7, 8, connected to a 40A breaker. Per Table E3705.5.3 [NEC240.4(D)] max OCPD for a #10 AWG conductor is 30A.
2) The Disconnect is the wrong size and only rated for 30A.
3) The sizing calcs for the max current of the existing are not correct by our calculations on PV-4, 4A, and 5.
07/20/2023 PDSD Application Completeness Express REVIEW COMPLETED