Permit Number: TC-RES-0723-06630
Parcel: 113081190

Review Status: Requires Resubmit

Review Details: RESIDENTIAL NEW DWELLING v.1

Permit Number - TC-RES-0723-06630
Review Name: RESIDENTIAL NEW DWELLING v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/27/2023 Site Engineering APPROVED
07/27/2023 Site Landscape NOT REQUIRED
08/03/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
08/03/2023 Residential Building REQUIRES RESUBMIT Building approval may not proceed without zoning approval.
Plans do not show existing service size or appropriate conductors sized for a 100 AMP sub panel. A electrical load calculation is required for validating service demand and sufficient service capacity.
07/27/2023 Site Zoning REQUIRES RESUBMIT FROM: Paul Camarena
PDSD Zoning Review Section

PROJECT: TC-RES-0723-06630
1027 E BLACKLIDGE DR Zoning R-2

TRANSMITTAL DATE:‎July 27, 2023


COMMENTS: Please resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

1.COMMENT:Clarify the use of the future project,
If this future project is for an RV pad, RV pads are not an allowed use in the R-2 Zone. At a minimum a Board of Adjustment for Variance would be needed to allow the use. Most likely a rezoning would be required. After discussions with staff the variance or rezoning would not be supported by staff. In the R-2 zone a personal RV may only be stored on site. The RV may not be hooked up to utilities and may not be occupied.

If you have any questions about this transmittal, Contact Paul Camarena at (520)837-4986 or by email Paul.Camarena@tucsonaz.gov
07/27/2023 PDSD Application Completeness Express REVIEW COMPLETED