Permit Number: TC-RES-0723-06617
Parcel: 122171540

Review Status: Requires Resubmit

Review Details: RESIDENTIAL NEW DWELLING v.3

Permit Number - TC-RES-0723-06617
Review Name: RESIDENTIAL NEW DWELLING v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
04/11/2024 Site Engineering APPROVED
04/16/2024 Site Zoning APPROVED
03/25/2024 Zoning Modifications - DDO APPROVED
04/16/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
03/26/2024 Residential Building REQUIRES RESUBMIT TC-RES-0723-06617 2nd
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide a separate Comment Response Letter when submitting updated plans. Facilitate a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

PROVIDE A COMPLETE PLAN SET showing all proposed alterations to the building with 2018 IRC code compliance with component sizes. The plans require sufficient detail for demonstrating an awareness of minimum building code compliance for passing all progress inspections.

PLANS:

1. The roof structure may not extend to a point closer than 3 feet from the neighboring property line without fire rated protection for fire spread. Provide compliance with R302.1 (City of Tucson Amended) by removing the roof placed within 3 feet to the property line or provide a complete wall barrier with not less than one-hour fire-resistive construction in compliance with IBC Table 721.1(2).

STRUCTURAL PLANS:

1. Ledger anchoring into an adobe structure is not included in the 2018 IRC. Provide an Arizona professional stamped plan set showing performance compliance, R301.1.

SECTIONS - DETAILS:

1. Provide a cross-section detail showing 2018 IRC compliant post foundations, R106.1. The 11-1/2” pier cannot provide a minimum 12” depth into earth and also extend untreated 6” above grade for supporting untreated wood, R317.1 item 5 and R403.1.4.

If you have any questions, please contact:
PDSD-Residential@tucsonaz.gov
City of Tucson Residential Plan Review

Submit a corrected plan set at https://www.tucsonaz.gov/Departments/Planning-Development-Services
03/15/2024 PDSD Application Completeness Express REVIEW COMPLETED