Permit Number: TC-RES-0723-06583
Parcel: 133403160

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SOLAR v.1

Permit Number - TC-RES-0723-06583
Review Name: RESIDENTIAL SOLAR v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/09/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
08/09/2023 Light Residential Building Review (OIP) REQUIRES RESUBMIT Permit Review TC-RES-0723-06583 (7739 E HAWTHORNE ST TUCSON, AZ 85710)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Residential Code (IRC).

1. Show the new 125A sub-panel in compliance with 705.12(B)(2)(3) b Busbars.) 120% bus bar rule. Where distribution equipment, including panelboards, is fed simultaneously by a primary source and one or more power source(s), and where the panelboard is capable of supplying multiple branch circuits or feeders, the interconnecting provisions for other power sources shall comply with 705.12(B)(1) through (B)(5).

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
Permit Review TC-RES-0723-06583 (7739 E HAWTHORNE ST TUCSON, AZ 85710)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Residential Code (IRC), 2017 National Electrical Code (NEC).

1. Show the new 125A sub-panel in compliance with 705.12(B)(2)(3) b Busbars.) 120% bus bar rule. Where distribution equipment, including panelboards, is fed simultaneously by a primary source and one or more power source(s), and where the panelboard is capable of supplying multiple branch circuits or feeders, the interconnecting provisions for other power sources shall comply with 705.12(B)(1) through (B)(5).
2. Provide/Show the feeder conductor size/type from the sub-panel and the main service panel.
3. Clarify what the 2nd utility meter is used for.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
07/18/2023 PDSD Application Completeness REVIEW COMPLETED