Permit Number: TC-RES-0723-06562
Parcel: 123030310

Address:
2832 E ELM ST

Review Status: Requires Resubmit

Review Details: RESIDENTIAL NEW DWELLING v.1

Permit Number - TC-RES-0723-06562
Review Name: RESIDENTIAL NEW DWELLING v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/07/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
08/07/2023 Residential Building REQUIRES RESUBMIT Permit Review TC-RES-0723-06562 (2832 E ELM ST TUCSON, AZ 85716)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Residential Code (IRC).

1. Verify the water heater circuit size for serving the load, E3702.11.
2. The addition of the new to the gas fired tankless WH, requires the submission of a gas pipeline template, G2401.1, R301.1: https://www.tucsonaz.gov/files/pdsd/permits/Gas_Piping_Template.pdf
See also: https://www.tucsonaz.gov/files/pdsd/permits/GAS_HANDOUT_2018_IRC_2019.2.4.pdf https://www.tucsonaz.gov/files/pdsd/permits/Sample_Gas_Template_0.pdf
Provide a complete gas piping template showing the connection from the meter to all gas appliances. Include pipe size, type and length. Provide appliance demands. G2413.4.1.
3. Provide the load rating, and manufacture’s specification sheets, of the combination washer/drier. Appliances and equipment on general purpose circuits may not exceed 50% of the branch circuit rating, E3702.5.
4. Show dryer vent size and location for venting to exterior, M1501. Or show in the manufacturer's specification sheet that this is an approved and listed unvented system.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
07/27/2023 Site Zoning REQUIRES RESUBMIT PDSD TRANSMITTAL
FROM: PDSD Zoning Review
PROJECT: TC-RES-0723-06562
2832 E Elm – R-1
Repair and remodel
TRANSMITTAL DATE: 07/27/2023

1. The subject structure located in the south east corner of the property is designated by Pima County Assessors Property Card as a structure used for storage only. Please provide documentation showing this structure being converted to a unit or clarify if the kitchen provided in the studio is a kitchenet (single basin sink, under the counter fridge, no cooking range). If it is a kitchenet then it can be approved as a sleeping quarter (not a unit) and no further documentation will be required.

Link to the assessor’s property card: https://www.asr.pima.gov/ParcelData/prc/12303/0310.pdf

Please reach out if you have any questions.

Resubmittal instructions: https://www.tucsonaz.gov/files/sharedassets/public/pdsd/documents/tdc-faq/new-pdfs/revisions-and-resubmittals.pdf

For questions regarding Zoning comments, please contact me at: Iman.Monshizadeh@tucsonaz.gov
07/20/2023 PDSD Application Completeness Express REVIEW COMPLETED
07/24/2023 Site Engineering REVIEW COMPLETED