Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/07/2023 | Commercial Building | APPROVED | |||
07/26/2023 | Site Engineering | APPROVED | |||
07/26/2023 | Site Zoning | APPROVED | |||
08/07/2023 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
08/01/2023 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical plan review comments and provide a written resonse. 1. The 3 phase Service Secondary feeders will require a Grounded Current Caring Conductor to be installed along with the Ungrounded Conductors NEC 250.24. 2. Indicate the Voltage, Phase, and Available Fault Current at the service on the line diagram. 3. Indicate the size of the MCB in panel ‘TEMP’. Ref; 2018 IBC section 107.2.1, 2017 NEC |
||
07/26/2023 | PDSD Application Completeness | REVIEW COMPLETED |