Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: TC-RES-0723-06505
Parcel: 119041150

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SOLAR v.1

Permit Number - TC-RES-0723-06505
Review Name: RESIDENTIAL SOLAR v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/04/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
08/04/2023 Light Residential Building Review (OIP) REQUIRES RESUBMIT Permit Review TC-RES-0723-06505 (3620 S BRONSON AV TUCSON, AZ 85713)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Residential Code (IRC), 2017 National Electrical Code (NEC).

1. OCPD for copper conductor may not exceed 30A for #10 AWG conductor, NEC 240.4(D)(small conductors). Use an #8 AWG conductor for raceway 4, 5 and 6, Sheet PV-5.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
07/13/2023 PDSD Application Completeness Express REVIEW COMPLETED