Review Status: Requires Resubmit
Review Details: RESIDENTIAL NEW DWELLING v.1
Permit Number - TC-RES-0723-06497
Review Name: RESIDENTIAL NEW DWELLING v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
07/19/2023 | Site Zoning | APPROVED | |||
07/26/2023 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
07/26/2023 | Residential Building | REQUIRES RESUBMIT | 1. Show receptacle outlets at each kitchen counter space wider than 12” with no point along the wall line more than 24” from a receptacle outlet, E3901.4.1. 2. Show two or more 2O AMP small appliance circuits at the kitchen countertop receptacle outlets; they may also serve the breakfast room and dining room, but not other locations, E3703.2 and E3901.3. 3. Show new or extended interior 15A & 20A circuits serving outlet locations (except garage, kitchen, and bathrooms) including receptacles, lights and smoke detectors with combination type arc-fault circuit interrupters, E3902.16 & 17. |
||
07/19/2023 | PDSD Application Completeness | REVIEW COMPLETED | |||
07/19/2023 | Site Engineering | REVIEW COMPLETED |