Review Status: Requires Resubmit
Review Details: RESIDENTIAL SIMPLE REVIEW v.1
Permit Number - TC-RES-0723-06487
Review Name: RESIDENTIAL SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
07/12/2023 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
07/12/2023 | Light Residential Building Review (OIP) | REQUIRES RESUBMIT | Permit Review TC-RES-0723-06487 (9901 E SHILOH ST TUCSON, AZ 85748) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2018 International Residential Code (IRC). PLUMBING Plans: 1. Note and specify all piping materials and sizes, P2609. 2. Provide total demand from all appliances. 3. Use Table G2413.4(1) (Metallic Pipe) to calculate correct required pipe sizes. (Use Table G2413.4(7) for Polyethylene plastic pipe). Assuming a Heater demand of 400,000 btuh, and a length of 50β, the 1β pipe is undersized. Minimum required size to the pool heater is 1 ΒΌβ. Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov |
||
07/12/2023 | PDSD Application Completeness | REVIEW COMPLETED |