07/07/2023 Light Residential Building Review (OIP) REQUIRES RESUBMIT Permit Review TC-RES-0723-06386 (1534 E MILES ST TUCSON, AZ 85719)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2017 National Electric Code (NEC).

1. Show a Service conductor sized per NEC 310.15(B)(7)(1), conductors supplying 100% of the load of a dwelling shall have an ampacity not less than 83% of the service rating. (200A * .83 = 166A).
2. Use NEC Table 310.15(B)(16), 75 degree C column, for sizing Service conductors, NEC 110.14(C). The 1/0 CU service conductor is undersized. (Ampacity rating of 1/0 CU = 150A which is less than 166A).

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov