Review Details: RESIDENTIAL SIMPLE REVIEW v.1
Permit Number - TC-RES-0723-06386
Review Name: RESIDENTIAL SIMPLE REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/07/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 07/07/2023 | Light Residential Building Review (OIP) | REQUIRES RESUBMIT | Permit Review TC-RES-0723-06386 (1534 E MILES ST TUCSON, AZ 85719) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2017 National Electric Code (NEC). 1. Show a Service conductor sized per NEC 310.15(B)(7)(1), conductors supplying 100% of the load of a dwelling shall have an ampacity not less than 83% of the service rating. (200A * .83 = 166A). 2. Use NEC Table 310.15(B)(16), 75 degree C column, for sizing Service conductors, NEC 110.14(C). The 1/0 CU service conductor is undersized. (Ampacity rating of 1/0 CU = 150A which is less than 166A). Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov |
||
| 07/07/2023 | PDSD Application Completeness Express | REVIEW COMPLETED |