Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL SIMPLE REVIEW v.1
Permit Number - TC-RES-0723-06333
Review Name: RESIDENTIAL SIMPLE REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/06/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 07/06/2023 | Light Residential Building Review (OIP) | REQUIRES RESUBMIT | Permit Review TC-RES-0723-06333 (9542 E CREEK ST TUCSON, AZ 85730) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2018 International Residential Code (IRC). 1. Show overcurrent protection not exceeding the allowable conductor ampacity, E3705.5. The 200A MSB is greater than the ampacity rating of the 4/0 AL conductor. 2. Use Table E3705.1, 75 degree C column, for sizing Service conductors. The 4/0 AL conductor between the Meter and the MSB is undersized. Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov |
||
| 07/06/2023 | PDSD Application Completeness Express | REVIEW COMPLETED |