Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: TC-RES-0626-03533
Parcel: 117066550

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SIMPLE REVIEW v.4

Permit Number - TC-RES-0626-03533
Review Name: RESIDENTIAL SIMPLE REVIEW v.4
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/17/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
07/17/2026 Light Residential Building Review (OIP) Express REQUIRES RESUBMIT If you have questions regarding this Review, please contact Juan Quintana at juan.quintana@tucsonaz.gov
Please resubmit addressing the following comment and resubmit along with a comment response letter:
1) Provide HVAC equipment model numbers, capacities, and efficiency ratings for compliance verification 2024 IECC R403.7
2) Provide fuel type and fuel demand, based on fuel type the following may be required:
Fuel Gas:
1) Include pipe size, type (Black Iron, Poly) and length. Show connections for gas meter to all gas appliances. Modifications to the gas system requires the submission of a gas pipeline template (or equivalent), G2401.1, G2413.1, R301.1
2) Size the pipe based on the length from the meter to the farthest attached appliance and max total demand of all attached appliances using Table G2413.4(1) (Metallic Pipe), Table G2413.4(7) Polyethylene Plastic Pipe. Note: The length is measured from the meter to the furthest attached appliance for all sizing, G2413.4.1.
See: https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/permits/residential-permits/gas_handout_2018_irc_2019.2.4.pdf
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/permits/residential-permits/gas_piping_template_060324.pdf
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/permits/residential-permits/gas_piping_sample_060324.pdf
Electric:
1) Provide a Load Calc. for the electrical including additional load from the new unit. NEC 220 Part III. Include conductors and all supplemental equipment used to supply the new central unit.
2) Outdoor receptacles supplied by a single-phase branch circuit must have GFCI protection for personnel E3902.3, 210.8(A)(3)
07/16/2026 PDSD Application Completeness Express REVIEW COMPLETED