Review Details: RESIDENTIAL SIMPLE REVIEW v.1
Permit Number - TC-RES-0626-03505
Review Name: RESIDENTIAL SIMPLE REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/26/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 06/26/2026 | Light Residential Building Review (OIP) Express | REQUIRES RESUBMIT | If you have questions regarding this Review, please contact Juan Quintana at juan.quintana@tucsonaz.gov Please resubmit addressing the following comments: 1) Provide load calculations including the additional load by the water heater (Standard or Optional is accepted). As of Jan. 1, the City of Tucson has adopted the 2024 I-codes and 2023 NEC. Verify that all calculations adhere to the variables present in the new code. 2)Verify if a grounded conductor (neutral) is required for the subpanel installation. Installation shall comply with NEC 110.3(B), 220.61, and 625.42. |
||
| 06/26/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |