Please resubmit addressing the following comments:
1) Provide Manufacturer Specifications of the EV charger to be used. Include any certifications to ensure that the EVSE is UL listed E404.14.1
2) Site plan does not clearly show the location of installation will be protected from impact. Show the location of the EV charger is protected from vehicular impact. E3404.10, 110.27(B)
3) EV charger must be GFCI-capable, alternatively provide a means of GFCI protection (including GFCI Overcurrent Protection Devices (OCPD)) 625.54
4) Indicate the rating of the overcurrent protective device (OCPD) to be installed on the plan set.