| 06/18/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 06/18/2026 | Light Residential Building Review (OIP) Express | REQUIRES RESUBMIT | Surge Protection must be listed in the plans If you have questions regarding this Review, please contact Juan Quintana at juan.quintana@tucsonaz.gov Please resubmit addressing the following comments: 1) Clarify scope of work to demonstrate if service panel will be replaced, upgraded, or repaired. 2) A Surge Protection Device (SPD) must be identified on the plans. This requirement can be satisfied by providing the manufacturer’s specifications for the SPD to verify that it is UL listed and code compliant E606.5 NEC 230.67 |
||