Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: TC-RES-0626-03217
Parcel: 141305500

Address:
6422 S INLAND DR

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SOLAR v.1

Permit Number - TC-RES-0626-03217
Review Name: RESIDENTIAL SOLAR v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/18/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
06/18/2026 Light Residential Building Review (OIP) - Standard REQUIRES RESUBMIT If you have questions regarding this Review, please contact Juan Quintana at juan.quintana@tucsonaz.gov

Please resubmit addressing the following comments:

1) The sum of supply sources (60A) exceeds the maximum allowable capacity (40A) for this 200A busbar rating, an additional derate is not permitted by code to adhere to 705.12. If a PMS system is used, please demonstrate the busbar setting and/or any additional information demonstrating adherence to NEC 705 and 750.
06/16/2026 PDSD Application Completeness Express REVIEW COMPLETED