Permit Number: TC-RES-0626-03215
Parcel: 134070520

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SIMPLE REVIEW v.1

Permit Number - TC-RES-0626-03215
Review Name: RESIDENTIAL SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/16/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
06/16/2026 Light Residential Building Review (OIP) Express REQUIRES RESUBMIT If you have questions regarding this Review, please contact Juan Quintana at juan.quintana@tucsonaz.gov

Please resubmit addressing the following comments:

1) A Surge Protection Device (SPD) must be identified on the plans. This requirement can be satisfied by providing the manufacturer’s specifications for the SPD to verify that it is UL listed and code compliant E606.5 NEC 230.67
2) Metal underground Fuel Gas piping system shall not be used as a grounding electrode. E3608.6 Revise plans and remove GEC from fuel gas piping system
06/16/2026 PDSD Application Completeness Express REVIEW COMPLETED