Permit Number: TC-RES-0626-03202
Parcel: 116185390

Address:
49 N MELWOOD AV

Review Status: Requires Resubmit

Review Details: RESIDENTIAL NEW DWELLING v.1

Permit Number - TC-RES-0626-03202
Review Name: RESIDENTIAL NEW DWELLING v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/01/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
07/01/2026 Residential Building REQUIRES RESUBMIT Willdan Engineering Phoenix
Ed Kulik
ekulik@willdan.com
1. Sheet 1 Provide structural calculations for masonry wall 7'
2. Sheet 1 Provide COT Special Inspection form listing the special inspector.
3. Sheet 6 Show water proofing at metal roof to ICF panel.
4. Sheet 6 Provide detail for attaching metal roofing through insulation.
5. Sheet 5 This project is in the City of Tucson.
6. Sheet 5 Provide installation instruction for the tankless water heater.
7. Sheet 10.1 Change to City of Tucson.
8. Sheet 11 Provide outdoor lighting calculations for the City of Tucson.
9. Sheet 11 Add City of Tucson.
10. Sheet 11 Provide GFCI outlet protection in the following locations; Laundry room wall outlet Dish washer outlet.
06/18/2026 Residential Engineering REQUIRES RESUBMIT Permit Activity Number: TC-RES-0626-03202 (1st Review)
Project: New S.F.R.
Location: 49 N MELWOOD AV
Review Date: 6/18/2026
Reviewer: Marco Contreras – Engineering Associate - Site Engineering
Reviewer Contact: Marco.contreras@tucsonaz.gov
Related cases:

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed to ensure final approval from Site Engineering.
To help speed up your resubmittal and facilitate shorter review timelines, please include a response letter along with your updated plans and any supporting calculations. In your response letter, address each comment individually and explain what changes were made and where they can be found in the plans. Please do not mark or highlight changes in the drawings at this stage — revision markups are only used after a permit has been issued. Submit your response letter and updated plan set as two separate files.
Site Engineering Review Comments:
1. The City of Tucson Inclusive Home Design Ordinance requires all new dwellings — including ADUs, single-family residences, and duplexes — to provide an accessible route connecting the public street, sidewalk, or driveway to an accessible entrance of the home. This pathway must be shown, dimensioned, and labeled on the plans. What this means in plain terms: There needs to be a clearly defined, walkable path from where a person arrives (the street, sidewalk, or driveway) all the way to a usable door of the home — one that someone using a wheelchair or mobility aid could navigate without barriers. An exterior accessible route that shall conform to 2017 ICC A117.1 Sections 402 and 403 and City of Tucson Inclusive Home Design Ordinance.
Reference: https://www.tucsonaz.gov/files/sharedassets/public/v/1/city-services/planning-development-services/documents/inclusivehomedesignordinance.pdf
Action Items — Show the following on your plans:
• Draw and label the path as "Accessible Route"
• Provide a minimum clear width of 4 feet with a width call-out on the plans
• Note the proposed running slope (must not exceed 5% / 1:20) and cross slope (must not exceed 2% / 1:50)
• Identify the accessible entrance the route leads to

Acceptable Accessible Route compositions include:
• Portland cement concrete (PCC)
• Broom Finished concrete
• Brick or unit pavers (Only if set on a stable cement base with no gaps exceeding ½”)
• Concrete pavers on concrete base (Same joint and evenness requirements as brick)
• Flagstone: must be mortared – loose set does not qualify
• Any surfaces equivalent in smoothness, hardness, and durability
NOTICE: Decomposed granite (DG) is not permitted for required accessible routes, even if compacted
06/22/2026 Residential Zoning REQUIRES RESUBMIT PDSD TRANSMITTAL

FROM: Roxanne Johnston
Planner
PROJECT: TC-RES-0626-03202
49 N Melwood Av., Tucson, AZ 85745
SFR (1st Review)

TRANSMITTAL DATE: 06/22/2026

This site is located within the R-2 Zone (UDC 4.7.9). A single-family residence is a permitted use in this zone (Table 4.8-2) subject to Use Specific Standards 4.9.7.B.6, .9, & .10.

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Correct plans, as noted in the comments below, along with a response letter indicating how all Site Zoning comments were addressed.

1. Please label the 20’ front setback off of N Melwood Av.
2. Label and show the information related to the driveway width. According to the subdivision plat for Melwood Place Lots 1-5 https://onbase.pima.gov/publicaccess/DS_NextGen_Single/etc/cq/results.html?cqid=240&OBKey__138_1=20192960278 , the east side (flag section) of the lot measures 6’, but the easement is 10’ and this needs to be shown on the site plan (Sheet 1).

3. The 7.5’ wide PUE and Access Easement need to be clearly labeled to the south of the lot per the plat.

4. Recalculate lot coverage. Per UDC 6.4.3.B., porches do not count towards total lot coverage. Vehicle use areas and enclosed structures do.

5. Dimension the vehicle use area.

6. The City of Tucson Inclusive Home Design Ordinance requires all new dwellings — including ADUs, single-family residences, and duplexes — to provide an accessible route connecting the public street, sidewalk, or driveway to an accessible entrance of the home. This pathway must be shown, dimensioned, and labeled on the plans. What this means in plain terms: There needs to be a clearly defined, walkable path from where a person arrives (the street, sidewalk, or driveway) all the way to a usable door of the home — one that someone using a wheelchair or mobility aid could navigate without barriers. An exterior accessible route that shall conform to 2017 ICC A117.1 Sections 402 and 403 and City of Tucson Inclusive Home Design Ordinance.
Reference: https://www.tucsonaz.gov/files/sharedassets/public/v/1/city-services/planning-development-services/documents/inclusivehomedesignordinance.pdf
Action Items — Show the following on your plans:
• Draw and label the path as "Accessible Route"
• Provide a minimum clear width of 4 feet with a width call-out on the plans
• Note the proposed running slope (must not exceed 5% / 1:20) and cross slope (must not exceed 2% / 1:50)
• Identify the accessible entrance the route leads to
Acceptable Accessible Route compositions include:
• Portland cement concrete (PCC)
• Broom Finished concrete
• Brick or unit pavers (Only if set on a stable cement base with no gaps exceeding ½”)
• Concrete pavers on concrete base (Same joint and evenness requirements as brick)
• Flagstone: must be mortared – loose set does not qualify
• Any surfaces equivalent in smoothness, hardness, and durability
NOTICE: Decomposed granite (DG) is not permitted for required accessible routes, even if compacted

7. Provide a landscape plan. Since January 1, 2026, via Ordinance No. 12219, landscaping is now required for all new single-family residential, middle housing development, and accessory dwelling units. A landscape plan is to be applied directly to the site plan and the instructions were designed to avoid hiring a landscape architect. Here is the instruction link: https://middle-housing-cotgis.hub.arcgis.com/pages/Residential-Landscaping-Code Essentially, one tree is required for the new ADU (1 tree per every 1,000 sf of new development, rounded up). Ground cover is required. To calculate ground cover, use the following equation: (X Linear feet of Street Frontage) – (Y curb cut width) x (5 Foot Depth) = Z sf of required vegetative groundcover.

8. List the plants (names) that will be used and the preferred method of watering to the site plan. Trees, which also need to be identified by name, need to be planted 5 feet from the sidewalk and 10 feet away from any structure. Additional requirements are provided in the link. Please make sure to refer to the link.

Plants must be low to very low water use with a hardiness rating of 15 degrees Fahrenheit or lower and non-invasive. Options are listed in Section 5-02.5.0 of the Technical Standards Manual. Exceptions to these criteria or plants that are not listed in Section 5-02.5.0 of the Technical Standards Manual, may be approved by the PDSD Landscape Architect.

The lot is irregular and staff recognize that the driveway with the front yard contain utilities. Per UDC 7.6.8.B.1.a, Exception: “If site constraints prevent new tree placement in a front yard, five shrubs may be substituted per required tree. Required trees must still be places elsewhere on the site. Shrubs used as a substitute plant material for the required tree shall range from three feet in height by three feet in width, or larger.”

9. Submit a response letter that addresses all staff comments.

10. Additional comments may be forthcoming depending on responses to zoning review comments and plans submitted for the next review.

If you have any questions about this transmittal, please contact Roxanne Johnston at roxanne.johnston@tucsonaz.gov .
06/18/2026 PDSD Application Completeness Express REVIEW COMPLETED