Permit Number: TC-RES-0626-03109
Parcel: 113050420

Address:
3508 N OLSEN AV

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SIMPLE REVIEW v.1

Permit Number - TC-RES-0626-03109
Review Name: RESIDENTIAL SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/11/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
06/11/2026 Light Residential Building Review (OIP) Express REQUIRES RESUBMIT If you have questions regarding this Review, please contact Juan Quintana at juan.quintana@tucsonaz.gov

Please resubmit addressing the following comments:
1) The generator exhaust must be 10 feet (3048 mm) from the property lines; 3 feet (914 mm) from exterior walls and roofs; 10 feet (3048 mm) from operable openings into buildings; 10 feet (3048 mm) above adjoining grade. Please show distances on plans adhering to 501.3.1
2) Verify an 80A back feed capable OCPD will be used from generator to subpanel.
3) Provide pipe material and length for each segment. G2401.1, G2413.1, R301.1
4) The new service panel has a connection to the service panel and one to the ATS. Clarify which source will back feed via hardwiring/lugs and via OCPD back feed. More comments may be forthcoming.
5) Provide a Load calc. for all loads to be transferred to the new load center to ensure all loads are adequately energized. Note, all conductors to be extended to the new panel must not exceed 40% fill of the 1-1/4" EMT.

Note: All DG interconnections must be reviewed and approved by TEP Design Services before installation. Contact (520) 918-8300
06/11/2026 PDSD Application Completeness Express REVIEW COMPLETED