Review Details: RESIDENTIAL SIMPLE REVIEW v.2
Permit Number - TC-RES-0626-03051
Review Name: RESIDENTIAL SIMPLE REVIEW v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/16/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 06/16/2026 | Light Residential Building Review (OIP) Express | REQUIRES RESUBMIT | If you have questions regarding this Review, please contact Juan Quintana at juan.quintana@tucsonaz.gov Please resubmit addressing the following comments: 1)The Breaker Schedule does not accurately provide the demand of the loads feeding to the entire dwelling. Provide a Load Calc. for the electrical including additional load from the new circuits using NEC 220 Part III. All circuits must be adequately energized to ensure code compliance. 2) GFCI Service receptacle must be provided within 25 ft of the HVAC system 210.63 |
||