Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL SOLAR v.1
Permit Number - TC-RES-0626-03048
Review Name: RESIDENTIAL SOLAR v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/10/2026 | Residential Zoning | APPROVED | |||
| 06/10/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 06/09/2026 | Light Residential Building Review (OIP) - Standard | REQUIRES RESUBMIT | If you have questions regarding this Review, please contact Juan Quintana at juan.quintana@tucsonaz.gov Please resubmit addressing the following comments: 1) Provide revised wind load calculations for the photovoltaic installation. Upon review, the submitted calculations indicate that the West Array (10 modules) does not demonstrate sufficient attachment pull-out capacity for the provided points of attachment (POAs). Based on the submitted design parameters, a minimum of sixteen (16) POAs would be required to satisfy the calculated uplift demands. Revise the array layout and attachment schedule or provide updated engineering documentation demonstrating compliance with the applicable wind load requirements of 2024 IRC Section R329 and the manufacturer's listed installation criteria. |
||
| 06/09/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |