Review Date Reviewer's Name Type of Review Description Status Comments
07/02/2026 Residential Engineering APPROVED
N/A Bldg Permits - Post Review Express PENDING ASSIGNMENT
N/A Residential Zoning PENDING ASSIGNMENT
06/30/2026 Residential Building REQUIRES RESUBMIT Please review the comments below and re submit.

1.R302.3.1 Dwelling unit separation: dwelling units shall be separated by fire-resistance rated assemblies that are vertical, horizontal, or a combination thereof.
R302.3.2 Fire resistance rating: a fire-resistance rating of 1-hour, OR a fire-resistance rating of one-half hour in buildings equipped throughout with an automatic sprinkler system. Use an assembly from International Building Code (IBC) Section 703.2.2
2.E3606.5 Surge protection: all services supplying dwelling units shall be provided with a surge-protective device (SPD) installed in accordance with Sections E3606.5.1 through E3606.5.3.
3.E3902.12 Appliance Outlets: GFCI protection is required for receptacle outlets or their branch circuit for:
1. Drinking water coolers
2. High pressure spray washing machines
3. Sump pumps
4. Dishwashers
5. Electric ranges
6. Wall-mounted ovens
7. Counter-mounted cooking units
8. Clothes dryers
9. Microwave ovens

4. Show smoke alarms locations.

5. Provide (an HVAC system with fresh air intake) whole-house mechanical ventilation with controlled exhaust, R303.4; N1103.6 & M1505.4. Show the minimum airflow rate setting and location of the device requiring this adjustable setting. A two or three-bedroom dwelling of 1501 – 3000 SF requires a 60 CFM continuous setting. A one-bedroom dwelling under 1501 SF requires a 30 CFM continuous setting.

6. Show an individual accessible water supply shut off for the proposed dwelling unit, P2903.9.1.
06/29/2026 PDSD Application Completeness Express REVIEW COMPLETED