Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL SIMPLE REVIEW v.1
Permit Number - TC-RES-0626-02985
Review Name: RESIDENTIAL SIMPLE REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/04/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 06/04/2026 | Light Residential Building Review (OIP) Express | REQUIRES RESUBMIT | If you have questions regarding this Review, please contact Juan Quintana at juan.quintana@tucsonaz.gov Please resubmit addressing the following comment: 1) Please clarify scope of work, specify if a service panel will be added or replaced. If the service panel supplying 100% of the electrical load to a dwelling is installed/replaced, it must adhere to 230.67. A SPD must be listed on the plans, this device must be a Type 1 or 2, UL 1449 Listed, and have a nominal discharge rating of at least 10kA. |
||
| 06/04/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |