Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: TC-RES-0626-02985
Parcel: 10602093A

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SIMPLE REVIEW v.1

Permit Number - TC-RES-0626-02985
Review Name: RESIDENTIAL SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/04/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
06/04/2026 Light Residential Building Review (OIP) Express REQUIRES RESUBMIT If you have questions regarding this Review, please contact Juan Quintana at juan.quintana@tucsonaz.gov

Please resubmit addressing the following comment:

1) Please clarify scope of work, specify if a service panel will be added or replaced.

If the service panel supplying 100% of the electrical load to a dwelling is installed/replaced, it must adhere to 230.67. A SPD must be listed on the plans, this device must be a Type 1 or 2, UL 1449 Listed, and have a nominal discharge rating of at least 10kA.
06/04/2026 PDSD Application Completeness Express REVIEW COMPLETED