Permit Number: TC-RES-0626-02921
Parcel: 120061260

Review Status: Requires Resubmit

Review Details: RESIDENTIAL ADD/ALT v.1

Permit Number - TC-RES-0626-02921
Review Name: RESIDENTIAL ADD/ALT v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/09/2026 Residential Building - Standard APPROVED
06/09/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
06/09/2026 Residential Zoning REQUIRES RESUBMIT PDSD TRANSMITTAL

FROM: Roxanne Johnston
Planner

PROJECT: TC-RES-0626-02921
408 E President St., Tucson, AZ 85714
Metal Carport (1st Review)

TRANSMITTAL DATE: 06/09/2026

This site is located within the R-2 Zone (UDC 4.7.9). A single-family residence is a permitted use in this zone (Table 4.8-2) subject to Use Specific Standards 4.9.7.B.6, .9, & .10.

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Correct plans, as noted in the comments below, along with a response letter indicating how all Site Zoning comments were addressed.

1. Submit a site plan. The plan set is missing a full site plan for zoning review. Please visit the following link and provide a Full site plan: https://www.tucsonaz.gov/Departments/Planning-Development-Services/Permits/Plan-Examples/Site-Plan-Examples.

2. Per Unified Development Code (UDC) 6.6.3.D.: Accessory structures, except for accessory dwelling units, shall not exceed 12 feet in height, unless attached to a principal structure. If attached, the maximum height permitted shall be the same as for the principal structure.

For the purposes of measuring height, Building height is the vertical distance measured from the design grade elevation to the highest point of a flat roof, to the deck line of a mansard roof, or to the middle (between the eave and ridge) of the highest gable of a pitched or hipped roof…(UDC 6.6.4.A.).

If the structure exceeds 12’, a variance from the Board of Adjustment will be required.

3. Provide a response letter addressing all review comments.

4. Additional comments may be forthcoming depending on responses to zoning review comments and plans submitted for the next review.

If you have any questions about this transmittal, please contact Roxanne Johnston at roxanne.johnston@tucsonaz.gov .
06/04/2026 PDSD Application Completeness Express REVIEW COMPLETED