Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: TC-RES-0626-02869
Parcel: 112063620

Address:
2234 E SILVER ST

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SIMPLE REVIEW v.1

Permit Number - TC-RES-0626-02869
Review Name: RESIDENTIAL SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/01/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
06/01/2026 Light Residential Building Review (OIP) Express REQUIRES RESUBMIT If you have questions regarding this request, please email PDSD-Permits@tucsonaz.gov

1) Please show or describe how whole home surge protection will be installed in the panel and resubmit.

Code references from the 2024 IRC are below:
E3606.5 Surge protection: all services supplying dwelling units shall be provided with a surge-protection device (SPD) installed in accordance with Sections E3606.5.1 through E3606.5.3. E3606.5.1 Location: the SPD shall be an integral part of the service equipment or shall be located immediately adjacent, if not located at each next-level distribution equipment downstream toward the load.

Step-by-Step instructions on how to resubmit:
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/tdc-faq/new-pdfs/revisions-and-resubmittals.pdf
06/01/2026 PDSD Application Completeness Express REVIEW COMPLETED