Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL SOLAR REVISION v.2
Permit Number - TC-RES-0625-03185
Review Name: RESIDENTIAL SOLAR REVISION v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/26/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 11/26/2025 | Light Residential Building Review (OIP) - Standard | REQUIRES RESUBMIT | Please resubmit responding to the following comments: 1) 1/0 XHHW (Copper) is capable of 170 A, please provide an updated conductor to adequately power the subpanel. NEC 230.42 2) Please provide spec sheets for Unirac railing For any questions, please email: PDSD-Residential@tucsonaz.gov |
||
| 11/13/2025 | Residential Zoning | REQUIRES RESUBMIT | Zoning comments not addressed in first revision cycle. Please See zoning comments for details. | ||
| 11/07/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |