Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL SIMPLE REVIEW v.1
Permit Number - TC-RES-0625-03178
Review Name: RESIDENTIAL SIMPLE REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/24/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 06/24/2025 | Light Residential Building Review (OIP) Express | REQUIRES RESUBMIT | ACTIVITY NO. TC-RES-0625-03178 ADDRESS/PARCEL: (238 E KELSO ST TUCSON, AZ 85705) Submit your revised reports along with a response letter which states how all Building Review Section comments were addressed. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. Review will not proceed without the response letter. COMMENTS: 1. Please show location of EV charger installation showing compliance with NEC 110.27 - (B) & 625.102. 2. Provide EV Charger spec sheet and/or show disconnecting means per NEC 625.43 and GFCI protection per NEC 625.54 3. Provide electrical load calculations which demonstrate that the premises electrical system has load capacity to accommodate the EV charging load (Include the EV charger in the load calculations as a continuous use item). See 2018 IRC E3704.2. 4. Please resubmit. Should you have any questions about these comments, I can be reached at ian.gillaspie@tucsonaz.gov. |
||
| 06/23/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |