Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL SIMPLE REVIEW v.1
Permit Number - TC-RES-0625-03066
Review Name: RESIDENTIAL SIMPLE REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/17/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 06/17/2025 | Light Residential Building Review (OIP) Express | REQUIRES RESUBMIT | PDSD Residential Review Section PROJECT: TC-RES-0625-03072 Run 50 feet of 1" PE pipe from meter to house. Run 1" black to first tee and run 3/4" black to stove, furnace and water heater.-(1st Review) (438 S OTERO AV) TRANSMITTAL DATE: June 17th, 2025 Comments: 1. The ¾” pipe is undersized for the given length and total appliance demand(205,000 BTU). Size the pipe based on the length from the meter to the farthest attached appliance and max total Branch demand of all attached appliances using Table G2413.4(1) 2. Minimum burial depth, 18” for PE pipe, G2415.12. 3.Yellow tracer wire required for PE pipe, G2415.17.3. Questions email building_official@tucsonaz.gov |
||
| 06/17/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |