Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL SIMPLE REVIEW v.1
Permit Number - TC-RES-0625-02992
Review Name: RESIDENTIAL SIMPLE REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/12/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 06/12/2025 | Light Residential Building Review (OIP) Express | REQUIRES RESUBMIT | ACTIVITY NO. TC-RES-0625-02992 ADDRESS/PARCEL: (3620 S HAMILTON PL TUCSON, AZ 85730) Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. Review will not proceed without the response letter. COMMENTS: 1. Please complete the Cooling Equipment Summary section in the Manual J. a. Please also provide the extended rating table for the HVAC unit. 2. This home was built in 1972, please change the construction quality on Manual J from “average” to “loose”. a. Correct every instance where this value appears 3. The assessor has the square footage at 934 sq ft and you have it listed as 1164 sq ft. Please list the correct square footage and adjust your Manual J calculation accordingly. 4. Please resubmit |
||
| 06/12/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |