Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: TC-RES-0625-02992
Parcel: 136234550

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SIMPLE REVIEW v.1

Permit Number - TC-RES-0625-02992
Review Name: RESIDENTIAL SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/12/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
06/12/2025 Light Residential Building Review (OIP) Express REQUIRES RESUBMIT ACTIVITY NO. TC-RES-0625-02992
ADDRESS/PARCEL: (3620 S HAMILTON PL TUCSON, AZ 85730)
Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. Review will not proceed without the response letter.
COMMENTS:
1. Please complete the Cooling Equipment Summary section in the Manual J.
a. Please also provide the extended rating table for the HVAC unit.
2. This home was built in 1972, please change the construction quality on Manual J from “average” to “loose”.
a. Correct every instance where this value appears
3. The assessor has the square footage at 934 sq ft and you have it listed as 1164 sq ft. Please list the correct square footage and adjust your Manual J calculation accordingly.
4. Please resubmit
06/12/2025 PDSD Application Completeness Express REVIEW COMPLETED