Permit Number: TC-RES-0624-03856
Parcel: 11306145A

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SIMPLE REVIEW v.3

Permit Number - TC-RES-0624-03856
Review Name: RESIDENTIAL SIMPLE REVIEW v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/03/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
07/03/2024 Light Residential Building Review (OIP) REQUIRES RESUBMIT Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2018 International Residential Code (IRC).

1) Please provide more information on the drawing showing what sections of pipe you are working on and what the repairs are that are being done. Also include pipe size, type, and length. Show connection, lengths, and sizes, from gas meter to all gas appliances. Modifications to the gas system requires the submission of a gas pipeline template (or equivalent), G2401.1, G2413.1, R301.1.
Gas Lines- Use Table G2413.4(1) (Metallic Pipe) to calculate correct required pipe sizes.
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/permits/residential-permits/gas_handout_2018_irc_2019.2.4.pdf
building_official@tucsonaz.gov
07/03/2024 PDSD Application Completeness Express REVIEW COMPLETED