Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: TC-RES-0624-03803
Parcel: 129063900

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SIMPLE REVIEW v.1

Permit Number - TC-RES-0624-03803
Review Name: RESIDENTIAL SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/26/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
06/26/2024 Light Residential Building Review (OIP) REQUIRES RESUBMIT Permit Review Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Residential Code (IRC), 2017 National Electrical Code (NEC).

1. Provide a site plan showing the location of the new Service Entrance location.
2. Show the location of the existing panel on the Site Plan and indicate if it will be a junction point for existing circuits or a sub-panel with a new feeder conductor from the new Service Entrance loaction, E3601.6.2 & E3705.8.

3. Provide the feeder conductor size and type feeding the sub panel. Conductors must be rated for direct burial or rated for wet location inside a conduit. Provide the OCPD size at the meter, E3702.3.


Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
06/26/2024 PDSD Application Completeness Express REVIEW COMPLETED