Permit Number: TC-RES-0624-03682
Parcel: 120092460

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SIMPLE REVIEW v.1

Permit Number - TC-RES-0624-03682
Review Name: RESIDENTIAL SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/18/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
06/18/2024 Light Residential Building Review (OIP) REQUIRES RESUBMIT PDSD Residential Review Section

PROJECT: TC-RES-0624-03682
Replace leaking original gas line-(1st Review)
(243 E Fairground Dr.)

TRANSMITTAL DATE: June 18th, 2024

COMMENTS:
Plan review for the above referenced structure has been completed. Please submit a gas piping template.

1. Include total developed length( Distance from meter to furthest appliance)
2. Include appliances with Btu for each.
3. Label all gas appliances with gas pipe sizes. Size the pipe based on the length from the meter to the farthest attached appliance and max total Branch demand of all attached appliances using Table G2413.4(1) (Metallic Pipe), Table G2413.4(7) (Polyethylene Plastic Pipe). Note: The length is measured from the meter to the furthest attached appliance for all sizing, G2413.4.1.

https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/permits/residential-permits/sample_gas_template_0.pdf

https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/permits/residential-permits/gas_handout_2018_irc_2019.2.4.pdf

Any questions please email building_official@tucsonaz.gov
06/18/2024 PDSD Application Completeness Express REVIEW COMPLETED