Permit Number: TC-RES-0624-03413
Parcel: 305978170

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SIMPLE REVIEW v.1

Permit Number - TC-RES-0624-03413
Review Name: RESIDENTIAL SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/06/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
06/06/2024 Light Residential Building Review (OIP) REQUIRES RESUBMIT Permit Review TC-RES-0624-03413 (12840 E TORTOISE POINTE DR VAIL, AZ 85641)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Residential Code (IRC), 2017 National Electrical Code (NEC).

1. Provide a panel schedule showing wire size and OCPD of each new circuit, E3702.2.
2. The conductors underground must comply with E3803.1 and be rated for use in a conduit in a wet location, E3803.10 i.e. THWN.
3. Designate the circuit number (that correlates to the panel schedule) at the location of the new equipment disconnect switch, E3404.12.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
06/06/2024 PDSD Application Completeness Express REVIEW COMPLETED