Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL SIMPLE REVIEW v.2
Permit Number - TC-RES-0624-03382
Review Name: RESIDENTIAL SIMPLE REVIEW v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/21/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 06/21/2024 | Light Residential Building Review (OIP) | REQUIRES RESUBMIT | Permit Review TC-RES-0624-03382 (7641 E 39TH ST TUCSON, AZ 85730) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2018 International Residential Code (IRC), 2017 National Electrical Code (NEC). 1. The approved plans show the first 90β of piping being replaced, but the new plans show a new furnace and total replacement of the gas line. The addition of the furnace to the gas system will require the piping to be upsized to meet the new total demand. Total demand = 174,000 BTU. The given length is 190β. Per Table G2413.4(1), you need 1 ΒΌβ pipe from the meter to the furnace/fireplace junction. 2. You will need to provide the length of pipe for each segment. That way you can size the pipe based on the longest length of pipe, measured from the meter to the farthest appliance, and not on the total length of pipe, G2413.4.1. |
||
| 06/21/2024 | PDSD Application Completeness Express | REVIEW COMPLETED |