Review Status: Approved
Review Details: RESIDENTIAL SOLAR v.2
Permit Number - TC-RES-0624-03333
Review Name: RESIDENTIAL SOLAR v.2
Review Status: Approved
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/07/2024 | Light Residential Building Review (OIP) | APPROVED | Approved with conductor sizing changed from #8 -> #6 (Sheets 4&5): Conductors shall be protected with OCPD’s having a rating not exceeding the allowable ampacity of the conductor, IRC E3705.5, reference NEC 310.15, 240.4. |
||
08/07/2024 | Bldg Permits - Post Review | REVIEW COMPLETED | |||
08/01/2024 | PDSD Application Completeness | REVIEW COMPLETED |