| 09/12/2023 | Light Residential Building Review (OIP) | REQUIRES RESUBMIT | For the line side connection, provide protection against overcurrent on the PV source conductors, 2017 NEC 690.9(B). Circuits connected to inverter’s output circuit (DG Disconnect) and also connected to a source having a higher current availability (utility power) shall be protected at the higher current source connection, 2017 NEC 690.9(A). Code reference, 2018 International Residential Code (IRC). 1. Provide a lag-bolt connection up-lift calculation demonstrating the wind load supporting capability for 115 MPH, or provide an engineer’s calculation, and sealed design, R301.1, R324.4. An IRC PV roof uplift calculator (XLS) is available on Pima County’s website. https://www.pima.gov/1069/Solar-Wind-Systems Contact Jamie Mason with any questions: Jamie.Mason2@tucsonaz.gov |
||