Permit Number: TC-RES-0623-06243
Parcel: 124130410

Address:
402 S FREMONT AV

Review Status: Requires Resubmit

Review Details: RESIDENTIAL NEW DWELLING v.3

Permit Number - TC-RES-0623-06243
Review Name: RESIDENTIAL NEW DWELLING v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
01/04/2024 Residential Building APPROVED
01/04/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
12/29/2023 Site Zoning REQUIRES RESUBMIT FROM: PDSD Zoning Review

PROJECT: TC-RES-0623-06243
402 S. Fremont Av. – R-2
New Accessory Dwelling Unit (ADU) (2nd Review)

TRANSMITTAL DATE: December 29, 2023

Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This site is located in the R-2 zone (UDC 4.7.9). A single-family residence (SFR) with an accessory dwelling unit (ADU) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.6, 8, & 9 and 6.6.3.

1. This comment was not addressed. The lot coverage calculation still includes porches and does not include vehicle use area. Per UDC Article 6.4.3.B.3.b vehicular use areas, measured within the outside edges of any area allocated to vehicle use, whether improved or unimproved. The lot coverage calculation is not correct. The lot size used 4,247 S.F. is not correct, based on a 50’ x 160’ lot the lot size should be 8,000 S.F.. Per UDC Article 6.4.3.C.1.a, Roofed areas, porches, open on at least one side and not included. Also per UDC Article 6.4.3.B.3.b any vehicle use area, whether improved or unimproved, is included.

2. This comment was not addressed. The Front Setback listed under Zoning Info: is not correct. Per UDC Article 6.4.5.C.1.a the setback should be 20’-0”.

3. This comment was not addressed. The side setback shown on the plot plan for the property line along Manlove St is not correct. Per UDC Article 6.4.5.C.1.b the setback should be 10’-0”.

4. This comment was not addressed. Per UDC Article 6.6.3.B.4 an ADU may not exceed 12’ in height. Building Height is the vertical distance measured from the design grade elevation to the middle (between the eave and ridge) of the highest gable of a pitched or hipped roof. See UDC Article 6.4.4.A & Figure 6.4.4-A. Provide a dimension of the elevations from design grade to the midpoint of the pitched room so that building heights can be verified.

5. This comment was not addressed. Clearly demonstrate that the requirements of UDC Article 6.6.3.B.2 and .3 are met for the proposed ADU.

COMMENTS: the following comments are relative to an application for a Design Development Option (DDO) (UDC 3.11.1).

Perimeter yard setbacks are based on a measurement from design grade to the highest point of the exterior wall UDC Article 6.4.5.B & Figure 6.4.5-A. As wall height dimensions were not provided from design grade to the highest point of the wall Zoning has used the 13’-11” dimension provided from finished floor to the peak of the roof.

1. This comment was not addressed. As dimensions from design grade to the highest point of the exterior wall Zoning will use the 12’-0” height shown on the elevations. 12’-0” x .6667 = a required perimeter yard setback of 8’-0”, proposed perimeter yard setback from the proposed ADU to the west property line is 7’-6”, a DDO is required. The minimum setback is the greater of six (6) feet, or two-thirds (2/3) the height of the structure’s wall facing each interior property line (Table 6.3-2.A). Based on the wall height of 13’-11” the required perimeter yard setback to the west property line is 9.3’ proposed setback is 7.5’. A Design Development Option (DDO) must be submitted and approved to reduce the required setback. DDO application and requirements can be found at: https://www.tucsonaz.gov/files/sharedassets/public/pdsd/documents/planning-amp-zoning/2019_ddo_for_setback_and_height_udc.pdf. If you have questions about the DDO application or process please contact Wyatt Berger at Wyatt.Berger@tucsonaz.gov or Georgia Pennington at Georgia.Pennington@tucsonaz.gov.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov
12/26/2023 PDSD Application Completeness Express REVIEW COMPLETED