Review Status: Requires Resubmit

Review Details: RESIDENTIAL SIMPLE REVIEW v.1

Permit Number - TC-RES-0623-06155
Review Name: RESIDENTIAL SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/28/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
06/28/2023 Light Residential Building Review (OIP) REQUIRES RESUBMIT Permit Review TC-RES-0623-06155 (962 S DUKE DR TUCSON, AZ 85710)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Residential Code (IRC).

1. Notate on the plans the full scope of work to include the new water heater.
2. Note and specify all piping materials and sizes, P2609. Show connection, lengths and sizes, from gas meter to all gas appliances.
3. Use G2413.4.1 Longest length method: Length is from Meter to the furthest connected appliance. Use this same length to determine all pipe sizes.
4. Use Table G2413.4(1) (Metallic Pipe) to calculate correct required pipe sizes. (Table G2413.4(7) Polyethylene Plastic Pipe). ¾” pipe size to the water heater is undersized for the given length and demand.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov