Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: TC-RES-0623-06083
Parcel: 116093280

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SIMPLE REVIEW v.3

Permit Number - TC-RES-0623-06083
Review Name: RESIDENTIAL SIMPLE REVIEW v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/10/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
07/10/2023 Light Residential Building Review (OIP) REQUIRES RESUBMIT Rev 2
Permit Review TC-RES-0623-06083 (1000 N CAMINO MIRAFLORES TUCSON, AZ 85745)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Residential Code (IRC).

1. Use Table G2413.4(7) (Polyethylene Plastic Pipe) to calculate correct required pipe sizes. Total Demand, 470 Cubic Feet per Hr (470,000 BTUh), longest length (from meter to furthest appliance) 160feet (use 175foot row in Table). From the meter to the pool heater requires a 2” poly pipe (first pipe with a capacity greater than the total demand).
2. Yellow tracer wire required for non-metallic pipe, G2415.17.3.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
07/10/2023 PDSD Application Completeness Express REVIEW COMPLETED