Permit Number: TC-RES-0623-06079
Parcel: 107111260

Review Status: Requires Resubmit

Review Details: RESIDENTIAL NEW DWELLING v.3

Permit Number - TC-RES-0623-06079
Review Name: RESIDENTIAL NEW DWELLING v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
12/21/2023 Site Zoning NOT REQUIRED
12/28/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
12/28/2023 Residential Building REQUIRES RESUBMIT This permit is for Unit #2. TC-RES-0623-06052 is the permit for Unit #1. The accessory building may be included on either permit usually associated with the closest dwelling.

1. Any structure placed in the 3-foot fire separation distance from the neighboring property line requires not less than one-hour fire-resistive construction for reducing fire spread across the property line, R302.1. Fire rated materials are found in IBC Table 721.1(2), Items 15-1.1 to 16-1.3 or relocate Unit #2 to a minimum of 3 feet from the property line.

2. The #6 feeder conductors are undersized. Provide a minimum service conductor rating of 100 AMP for each dwelling and conductors with minimum rating of #3 copper 75 degree C, E3602.1 & E3603.1.

3. Show two or more 2O AMP small appliance circuits at the kitchen countertop receptacle outlets; they may also serve the breakfast room and dining room, but not other locations, E3703.2 and E3901.3.

4. Show Bathroom receptacles with a separate 20 AMP dedicated circuit, E3703.4 and E3901.6.

5. Smoke alarms are required outside each separate sleeping area, R314.3.2. Show a smoke alarm in each bedroom and outside the doorway in the immediate vicinity.
12/18/2023 PDSD Application Completeness Express REVIEW COMPLETED