Review Status: Requires Resubmit
Review Details: RESIDENTIAL NEW DWELLING v.3
Permit Number - TC-RES-0623-06079
Review Name: RESIDENTIAL NEW DWELLING v.3
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/21/2023 | Site Zoning | NOT REQUIRED | |||
| 12/28/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 12/28/2023 | Residential Building | REQUIRES RESUBMIT | This permit is for Unit #2. TC-RES-0623-06052 is the permit for Unit #1. The accessory building may be included on either permit usually associated with the closest dwelling. 1. Any structure placed in the 3-foot fire separation distance from the neighboring property line requires not less than one-hour fire-resistive construction for reducing fire spread across the property line, R302.1. Fire rated materials are found in IBC Table 721.1(2), Items 15-1.1 to 16-1.3 or relocate Unit #2 to a minimum of 3 feet from the property line. 2. The #6 feeder conductors are undersized. Provide a minimum service conductor rating of 100 AMP for each dwelling and conductors with minimum rating of #3 copper 75 degree C, E3602.1 & E3603.1. 3. Show two or more 2O AMP small appliance circuits at the kitchen countertop receptacle outlets; they may also serve the breakfast room and dining room, but not other locations, E3703.2 and E3901.3. 4. Show Bathroom receptacles with a separate 20 AMP dedicated circuit, E3703.4 and E3901.6. 5. Smoke alarms are required outside each separate sleeping area, R314.3.2. Show a smoke alarm in each bedroom and outside the doorway in the immediate vicinity. |
||
| 12/18/2023 | PDSD Application Completeness Express | REVIEW COMPLETED |