Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: TC-RES-0623-05955
Parcel: 12616338B

Address:
4117 E BROWN WY

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SIMPLE REVIEW v.1

Permit Number - TC-RES-0623-05955
Review Name: RESIDENTIAL SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/20/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
06/20/2023 Light Residential Building Review (OIP) REQUIRES RESUBMIT Permit Review TC-RES-0623-05955 (4117 E BROWN WY TUCSON, AZ 85711)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Residential Code (IRC).

1. Note and specify all piping materials and sizes, P2609.
2. Use Table G2413.4(1) (Metallic Pipe) to calculate correct required pipe sizes. (Table G2413.4(7) Polyethylene Plastic Pipe).
3. Minimum burial depth, 12”, G2415.12.
4. Yellow tracer wire required for non-metallic pipe, G2415.17.3.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
06/15/2023 PDSD Application Completeness Express REVIEW COMPLETED