Permit Number: TC-RES-0623-05937
Parcel: 114510440

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SIMPLE REVIEW v.3

Permit Number - TC-RES-0623-05937
Review Name: RESIDENTIAL SIMPLE REVIEW v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/05/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
10/05/2023 Light Residential Building Review (OIP) REQUIRES RESUBMIT Permit Review TC-RES-0623-05937 (2530 N TANQUE VERDE ACRES DR TUCSON, AZ 85749) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2018 International Residential Code (IRC). • 2017 National Electrical Code (NEC).

>>> these comments were unaddressed. If the solar system is going into any panel it needs to meet the corresponding code requirements of the NEC. The plans submitted do not allow for code compliance verification.

1. Provide a 3-line diagram identifying each component and circuit notating sizes and installation details. OCPD, wire type and conductor size.
2. Provide Main Service Panel (MSP) and Sub panel taps in compliance with NEC 705* (NEC 705.12) 705.12(B)(2)(3) b Busbars.) 120% bus bar rule.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov