Permit Number: TC-RES-0623-05935
Parcel: 112063730

Review Status: Requires Resubmit

Review Details: RESIDENTIAL NEW DWELLING v.1

Permit Number - TC-RES-0623-05935
Review Name: RESIDENTIAL NEW DWELLING v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/16/2023 Site Engineering NOT REQUIRED
07/12/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
07/12/2023 Residential Building REQUIRES RESUBMIT TC-RES-0623-05935

PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. For facilitating a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment updates; revisions are processed if changes occur after the permit is issued.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:

The City of Tucson adopted the 2018 IRC with amendments on 1/1/2019. Show the current code reference on the plans.

Provide a complete construction plan set showing 2018 IRC compliance, R106.1.

An independent dwelling (ADU) requires fire spread and utility (electrical & water) separation so that one dwelling is not dependent upon another for water or electrical service.

Each dwelling unit with kitchen requires a separate Pima County assigned street address after Zoning approval, R319.

An impact fee payment is required for an ADU at time of permit payment.
reinforcement, etc.

SITE PLAN:

1. Show the location and size of buildings, utility meters and gas, water, electric and sewer or septic lines from property line to building, R106.1.1. Each dwelling requires an independent electrical service and water supply shut off devices. Identify the utility lines requiring upgrade or replacement.
2. Show a street address for each dwelling on the site plan, R319.

PLANS:

1. Show one-hour fire-resistive framed construction separating dwellings in compliance with IBC Table 721.1(2).

PLUMBING PLANS:

1. Tucson Water Department limits flow rates for each water meter size in compliance with P2903.7. Show an appropriate yard pipe for supporting the existing and proposed dwellings and show an appropriate water meter size.
2. Show an individual accessible water supply shut off and water heater for the proposed dwelling unit, P2903.9.1..

MECHANICAL PLANS:

1. Show the HVAC system location and size for the building demand in accordance with M1401.3, M1601.1.
2. Provide (an HVAC system with fresh air intake) whole-house mechanical ventilation, or controlled exhaust with a calculated airflow rate, R303.4; N1103.6 & M1505.4. Show the system and appropriate flow rate setting on the plans. A one bedroom dwelling under 1501 SF requires a 30 CFM continuous setting.
3. Provide demand calculations in accordance with Manual J/S/D standards, M1401.3, M1601.1. Systems shall be sized in accordance with Manual S based on building loads calculated in accordance with Manual J and duct systems sized in accordance with Manual D. Notate if the mechanical plans if system calculations will be provided by deferred submittal.

ELECTRICAL PLANS:

1. Provide a Riser Diagram showing an accessible Service Disconnect for each dwelling unit, E3601.6.2.
2. Provide a panel schedule showing panel size, circuit numbers, ampacity, wire size and general description, E3404.13 & E3706.2. Provide a panel schedule showing wire size of each circuit or notate the wire size for each protection rating, E3702.2.
3. Provide separation of all circuits for each dwelling unit, E3601.3. Conductors may not pass through another dwelling unit.
4. Show the location of the service disconnect outside of the building or inside nearest the point of entrance where each occupant has ready access, E3601.6.2 & E3705.8.

INTERNATIONAL ENERGY CONSERVATION CODE:

1. Energy Certificate: (Mandatory) place near the indoor furnace or in utility room, N1101.14. Add notation to plans.

Please contact the plans reviewer if you have any questions:
Ken Van Karsen
PDSD-Residential@tucsonaz.gov
City of Tucson Residential Plan Review
06/23/2023 Site Zoning REQUIRES RESUBMIT FROM: PDSD Zoning Review

PROJECT: TC-RES-0623-05935
2202 E. Spring St. – R-2
Convert SFR to SFR with Accessory Dwelling Unit (1st Review)

TRANSMITTAL DATE: June 23, 2023

Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This site is located in the R-2 zone (UDC 4.7.9). An SFR with an ADU is a permitted use in the zone, (Table 4.8-2), subject to Use Specific Standards 4.9.7.B.6, .9, & .10 & 6.6.3

1. Provide a residential plot plan that meets the requirements found at: https://www.tucsonaz.gov/files/pdsd/forms/Residential_Plot_Plan_Requirements.pdf.

2. Clearly demonstrate that all requirements of UDC Article 6.6.3 are met for the ADU

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov
06/16/2023 PDSD Application Completeness Express REVIEW COMPLETED