Permit Number: TC-RES-0623-05908
Parcel: 121113030

Address:
1138 N NEMA AV

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SOLAR v.1

Permit Number - TC-RES-0623-05908
Review Name: RESIDENTIAL SOLAR v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/07/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
07/07/2023 Light Residential Building Review (OIP) REQUIRES RESUBMIT Permit Review TC-RES-0623-05908 (1138 N NEMA AV TUCSON, AZ 85712)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Residential Code (IRC).

1. Show overcurrent protection less than or equal to the allowable conductor ampacity, E3705.5. Revise the breaker or wire size shown for Wire Tag E, Sheet PV-4 and PV-5.
2. Use Table E3705.1, 75 degree C column, for sizing branch circuits and conductors rated greater than 100 AMP, E3705.4.2.
3. Clarify the connection of the backup load panel. Sheet PV-3.2 shows a “Relocated loads conduit” AND a connection to the 200A Enphase IQ system controller. Sheets PV-4/5 only show the 200A Enphase IQ system controller connecting to the backup load panel.
4. Clarify the type of PV disconnect being used. The EATON DG222URB is shown with a 100A fused disconnect on Sheet PV-3.2, but shown as a 60A non-fused disconnect on sheets PV-4/5.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov